Gas-fired infrared
space heaters shall be furnished and installed in accordance with
governing codes and as shown per building drawing(s) as described
below:
Heaters shall be SPACE-RAY CB series tube heaters,
model number(s) CB_________, rated at _____________ Btu/hr as
manufactured by Gas-Fired Products, Inc., Charlotte, North Carolina.
Heaters shall be equipped with a 24-volt direct spark ignition
with automatic 100% shutoff system. Power supplied to each heater
shall be 120 VAC, 60 Hz. The heater controls shall include a pressure
switch designed to provide complete unit shutoff in the event
of combustion air or flue blockage. The heaters shall be equipped
with an on-line diagnosis monitoring light system. The three lights
shall monitor the power to the heater, insufficient airflow, and
the spark ignition and the combination gas valve operation.
The heater's burner shall consist of a cast iron
atmospheric burner. The flame characteristics shall be highly
luminous for maximum radiant heat transfer through the emitter
tube wall.
The heater's emitter tube shall
operate at an average surface temperature of 750ºF and shall be made of
16-gauge, aluminized steel for long life (3" O.D.). The
emitter tube shall be calorized for longevity, corrosion resistance,
and high radiant efficiency. The measured surface emissivity
shall be 0.83 - 0.86 at operating temperature. The calorization
process shall produce an emitter tube that is highly radiant
absorptive (0.95) on the interior and highly radiant emissive
(0.83-0.86) on the exterior.
To assure a high degree of safety and increased
radiant efficiency, the heaters shall operate under negative pressure
at all times during operation to preclude the escape of combustion
gases inside the building. The heater exhaust assembly shall include
a 120-volt draft inducer. The draft inducer shall be equipped
with a permanently lubricated, totally enclosed and shielded,
fan cooled, and heavy-duty ball bearing motor. The motor shall
not require maintenance or lubrication for the life of the unit.
The draft inducer assembly shall be capable of rotating 90o for
vertical or horizontal venting.
The heaters will be CSA design certified for vertical
or horizontal venting, maximum 75 feet horizontal sidewall venting,
and for 50 feet outside combustion inlet duct. There shall be
no draft hoods. The combustion chamber shall be totally enclosed.
The heaters shall utilize factory assembled, highly
efficient aluminum reflectors with a reflectivity of 97.5%. The
reflector ends shall be enclosed for maximum radiant heat output
and minimum convection losses. The tube body and U-bend shall
be totally enclosed with reflectors to maximize emitter temperature.
The single reflector design shall cover the firing and exhaust
legs as well as the u-bend.
The heaters shall be factory assembled and tested.
The heaters shall not require any field wiring or adjustments
to assure maximum performance and safety.
Heaters shall operate satisfactorily
in any position from horizontal to forty-five degrees (45º)
from horizontal, and shall be suitable for vented/indirect
vented applications. Heaters shall be designed to operate on
natural or propane gas.
Heaters shall be design certified by the Canadian
Standards Association (CSA) to American National Standard Z83.20/CSA
2.34. The manufacturer shall provide a written limited warranty
covering the heavy one-piece cast iron burner for a period of
ten (10) years, the emitter tube for a period of five (5) years,
and all components utilized in the heater's control assembly for
a period of one (1) year.