Architectural
/ Engineering Short Form Specifications
for Infrared Radiant Heaters for Industrial and/or Commercial Applications
RSTP
Series Short Form Specs |
TUBE HEATERS: RSTP
Series
Gas-fired infrared
space heaters shall be furnished and installed in accordance with
governing codes and as shown per building drawing(s) as described
below:
Heaters shall be SPACE-RAY RSTP
series tube heaters, model number(s) RSTP_________, rated at ____________
Btu/hr as manufactured by Gas-Fired Products, Inc., Charlotte, North
Carolina. Heaters shall be equipped with a 24-volt direct spark ignition
system with automatic 100% gas shutoff, redundant combination gas valve,
and a diaphragm switch designed to complete unit shutoff in the event
of combustion air or flue blockage. The heaters shall be equipped with
three on-line diagnosis monitoring lights to monitor the power to the
heater, insufficient air flow, and the spark ignition and combination
gas valve operation. Power supplied to each heater shall be 120 VAC,
60 Hz.
The heater's burner shall consist
of a cast iron atmospheric burner with stainless steel flame retainer
and shall utilize an aluminized steel entrance cone and support assembly,
which will maintain a uniform air annulus around the flame pattern.
The flame characteristics shall be highly luminous for maximum radiant
heat transfer through the emitter tube wall.
The heater's emitter tube shall
operate at an average surface temperature of 900ºF and shall be
made of 16-gauge, 4" O.D. aluminized steel for long life. The emitter
tube shall be calorized for longevity, corrosion resistance and high
radiant efficiency. The minimum input firing rate shall be 7,000 Btu/hr
per square foot of emitter tube surface. The measured surface emissivity
shall be 0.83 - 0.86 at operating temperatures. The calorization process
shall produce an emitter tube that is highly radiant absorptive (0.95)
on the interior and highly radiant emissive (0.83-0.86) on the exterior.
To assure a high degree of safety
and increased radiant efficiency, the heaters shall operate under negative
pressure at all times during operation to preclude the escape of combustion
gases inside the building. The heater exhaust assembly shall include
a 120-volt draft inducer. The draft inducer shall be equipped with a
permanently lubricated, totally enclosed and shielded, fan cooled, and
heavy-duty ball bearing motor. The motor shall not require maintenance
or lubrication for the life of the unit.
The heaters shall utilize factory
assembled, highly efficient aluminum reflectors with a reflectivity
of 97.5%. The reflector ends shall be enclosed for maximum radiant heat
output and minimum convection losses. The heaters shall be completely
factory assembled and tested. The heaters shall not require any field
wiring, adjustments or assembly to assure maximum performance and safety.
Heaters shall operate satisfactorily in any position from horizontal
to ninety degrees (90º) from horizontal, and shall be suitable
for vented/indirect vented and inside/outside applications. Heaters
shall be designed to operate on natural or propane gas.
Heaters shall be design certified
by the Canadian Standards Association (CSA) to American National Standard
Z83.20/CSA 2.34. The manufacturer shall provide a written limited warranty
covering the cast iron burner for ten (10) years, the emitter tube for
five (5) years, and all other components for one (1) year.